Polyamide Glands for Ex e Applications

BM-X2L

M20x1,5 / 6,0-12,0mm / TL=15,0mm

ATEX
IMQ 13 ATEX 010X | EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-7:2015, EN 60079-31:2014 
IECEx
IECEx IMQ 13.0003X | IEC 60079-0:2011 ; IEC 60079-7:2006-07 ; IEC 60079-31:2013
TR RU
No TC RU C-TR.AA87.B.00941 | ГОСТ 31610.0-2014 ГОСТ IEC 60079-1:2013 ГОСТ IEC 60079-31:2013
IN METRO
DNV 18.0150 X | ABNT NBR IEC 60079-0:2013, ABNT NBR IEC 60079-7:2008 ABNT NBR IEC 60079-31:2011
MARINE APPROVAL
TAE00003WV | IEC/EN60079-0, IEC/EN60079-7, IEC/EN60079-31 IEC/EN 62444
Products specifications
Material Body , Cap PA 6 (Polyamide 6)
Seal CR (Chloroprene) , Silicone
Ingress Protection Rating
IP 68 - 5 Bar, 30 min
IP 66
Operating Temperature Seal Material
CR (Chloroprene) Silicone
Ex e/tb / Ex tb -40°C to +80°C -60°C to +80°C
Equipment For
Gas & Dust potentially explosive atmospheres
Cable glands should be also used for intrinsically safe circuits Ex-i.
These cable glands shall have a light blue colored cap. The symbol " I" will -
be added beside of the "BM" for order processing.
Suitable for use in
Group II Gas Group IIC ZONE1/ZONE2
Group III Dust Group IIIC ZONE21/ZONE 22
Equipment Marking
Ex II 2GD
Ex eb IIC Gb Ex tb IIIC Db
Marking Example *
BMD BM-X... CE 0722 2GD Ex eb IIC Gb Ex tb IIIC Db IP66/68
Ta-40°C +80°C IMQ 13 ATEX 010X IECEx IMQ 13.0003X
Impact Test Result 4J
Thread Type
Metric (M) ISO Pitch 1,5
NPT (N) ANSI ASME B1.20.1
PG (P) DIN 40430
Other thread types also available upon request.
Cable Type Non Armoured
Accessories Lock nuts
Gaskets ( Washers )
Dome plugs
Dust Plugs
Double Seals
Remarks We recommend the use of locknuts and gaskets to ensure IP rating for rough
surfaces or through holes.
Accessories must be ordered separately.
Outer Thread Size (Male) M20x1,5
Thread Length (TL) 15,0 mm
Ø (D) 27,0 mm
Clamping Range Outer Sheath Ø min - max 6,0 - 12,0 mm
Spanner Width Cap 24 mm
Body 24 mm
max. Height (H) 32,4 mm
Part Number BM-X2L
Order Coding
Part Number
Mandatory
Seal
Mandatory
Gasket (Washer)
Option
Seal Type
Option
Lock Nut
Option
Sealing Plug
Option
See table
*Part number for blue cap is BMI-..
C Chloroprene
WC Chloroprene
WF Fiber
WS Silicone
Double
Seal
L Lock nut
P Dome Plug
Example
BM-X2L C WC DS L P
*BMI-X3